SYSDrive Frequency Inverter
T
V/f control
T
PID control
T
Standard LED, optional LCD operator
T
Fieldbus options: DeviceNet
T
7 configurable digital inputs
T
3 configurable digital outputs
T
Low audible noise
T
Powerful application oriented functionality
T
High slip braking
T
Easy maintenance
T
Energy saving function
3G3PV
Ordering Information
3G3PV-
VV VVV
- E
A2
B4
kW
Product code
Example: 3G3PV - A4007-E
SYSDrive 3G3PV Inverter
Description
A = IP20, B = IP00, 2 = 200V Type, 4 = 400V Type
I537-E2-01
3G3PV High-function General-purpose Inverters for Variable Torque Applications User’s Manual
T
200-V Class Inverters
3G3PV-
A
2004 2007 2015 2022 2037 2055 2075 2110 2150 2185 2220 2300 2370
0.75
1.6
4.1
1.5
2.7
7.0
2.2
3.7
9.6
3.7
5.7
15
5.5
8.8
23
7.5
12
31
11
17
45
15
22
58
18.5
27
71
22
32
85
30
44
115
37
55
145
Max. applicable motor output (kW) (note 1)
0.4
Output ratings
Rated output capacity (kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency (Hz)
Rated voltage (V)
Rated frequency (Hz)
Allowable voltage fluctuation
Allowable frequency fluctuation
Measures for
power supply
harmonics
DC reactor
12-phase
rectification
Not possible
1.2
3.2
Specifications
3-phase; 200, 208, 220, 230 or 240 VAC
(Proportional to input voltage.)
120 Hz max.
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
-15% to +10%
±5%
Optional
Built in
Possible (note 2)
Control Power supply
Note
1.
The maximum applicable motor output is given for a standard 4-pole OMRON motor. When selecting the actual motor
and Inverter, be sure that the Inverter's rated current is applicable for the motor's rated current.
2.
A 3-wire transformer is required on the power supply for 12-phase rectification.
1
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
3G3PV
3G3PV
3G3PV-
Max. applicable motor output (kW) (note 1)
Output ratings
Rated output capacity (kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency (Hz)
Rated voltage (V)
Rated frequency (Hz)
Allowable voltage fluctuation
Allowable frequency fluctuation
Measures for
power supply
harmonics
DC reactor
12-phase rectification
A
B
2450 2550 2750 2900 2220 2300 2370 2450 2550 2750 2900 211K
45
69
180
55
82
215
75
110
283
90
130
346
22
32
85
30
44
115
37
55
145
45
69
180
55
82
215
75
110
283
90
130
346
110
160
415
3-phase 200, 208, 220, 230 or 240 VAC
(Proportional to input voltage)
120 Hz max.
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
+ 10%, - 15%
±5%
Built in
Possible (note 2)
T
400-V Class Inverters
3G3PV-
Max. applicable motor output (kW) (note 1)
Output ratings
Rated output capacity (kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency (Hz)
Rated voltage (V)
Rated frequency (Hz)
Allowable voltage fluctuation
Allowable frequency fluctuation
Measures for
power supply
harmonics
DC reactor
12-phase rectification
A
4004 4007 4015 4022 4037 4040 4055 4075 4110 4150
0.4
1.4
1.8
0.75
1.6
2.1
1.5
2.8
3.7
2.2
4.0
5.3
3.7
5.8
7.6
4.0
6.6
8.7
5.5
9.5
12.5
7.5
13
17
11
18
24
15
24
31
4185
18.5
30
39
Control Power supply
3-phase; 380, 400, 415, 440, 460 or 480 VAC
(Proportional to input voltage.)
120 Hz max.
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
+ 10%, - 15%
±5%
Optional
Not possible
Control Power supply
3G3PV-
Max. applicable motor output (kW) (note 1)
Output ratings
Rated output capacity (kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency (Hz)
Max. voltage (V)
Rated frequency (Hz)
Allowable voltage fluctuation
Allowable frequency fluctuation
Measures for
power supply
harmonics
DC reactor
12-phase rectification
A / B
4220
22
34
45
4300
30
46
60
4370
37
57
75
4450
45
69
91
4550
55
85
112
4750
75
110
150
4900
90
140
180
411K
110
160
216
413K
132
200
260
416K
160
230
304
3-phase, 380, 400, 415, 440, 460 or 480 VAC
(Proportional to input voltage.)
120 Hz max.
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
+ 10%, - 15%
±5%
Built in
Possible (note 2)
Control Power supply
Note
1.
The maximum applicable motor output is given for a standard 4-pole OMRON motor. When selecting the actual motor
and Inverter, be sure that the Inverter's rated current is applicable for the motor's rated current.
2.
A 3-wire transformer is required on the power supply for 12-phase rectification.
2
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
3G3PV
3G3PV
T
Common Specifications
3G3PV-
Control method
Speed control range
Speed control accuracy
Frequency accuracy
(temperature characteristics)
Frequency setting
resolution
Overload capacity and
maximum current (note 1)
Frequency setting signal
Acceleration/Deceleration time
Sine wave PWM
V/f control
1:40
±2 to 3% (25°C ± 10°C)
Digital references: ± 0.01% (-10°C to +40°C)
Analog references: ±0.1% (25°C ±10°C)
Digital references: 0.01 Hz
Analog references: 0.05/50 Hz (10 bit no sign)
120% of rated output current per minute
0 to 10 V, 4 to 20 mA
0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration setings)
Restarting for momentary power loss, speed searches, overtorque detection, 4-speed control
(maximum), acceleration/deceleration time changes, S-curve acceleration, 3-wire sequence, au-
totuning, cooling fan ON/OFF control, torque compensation, jump frequencies, upper and lower
limits for frequency references, DC braking for starting and stopping, high-slip braking, PI control
(with sleep function), energy-saving control, RS-422A/485 communications (19.2 kbps maxi-
mum), fault reset and function copying.
Protection by electronic thermal overload relay.
Stops for fuse blown.
120% of rated output current for 1 minute
200 Class Inverter: Stops when main-circuit DC voltage is above 410 V.
400 Class Inverter: Stops when main-circuit DC voltage is above 820 V.
200 Class Inverter: Stops when main-circuit DC voltage is below 190 V.
400 Class Inverter: Stops when main-circuit DC voltage is below 380 V.
Stops for 15 ms or more.
By selecting the momentary power loss method, operation can be continued if power is restored
within 2 s.
Protection by thermistor.
Stall prevention during acceleration, deceleration or running.
Protection by electronic circuits. (50% of inverter rated current)
Lit when the main circuit DC voltage is approx. 50 V or more.
Indoor (no corrosive gas, dust, etc.)
-10°C to 40°C (Enclosed wall-mounted type)
-10°C to 45°C (Open chassis type)
95% max. (with no condensation)
- 20°C to + 60°C (short-term temperature during transportation)
1000 m max. (note 2)
10 to 20 Hz, 9.8 m/s
2
max.; 20 to 50 Hz, 2 m/s
2
max
Enclosed wall-mounted type (NEMA 1): 18.5 kW or less (same for 200 V and 400 V class)
Open chassis type (IP00): 22 kW or more (same for 200 V and 400 V class Inverters)
Specification
Control characteristics
Protective function
Environment
Note
Main control functions
Motor protection
Fuse blown protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power loss
ridethru
Cooling fin overheating
Stall prevention
Grounding protection
Charge indicator
Application site
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Vibration
Protective structure
1.
Increase the Inverter capacity if loads exceeding these current values are expected.
2.
If applied in higher altitudes contact your OMRON representative.
3
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
3G3PV
3G3PV
T
Digital Operators
Digital Operator with LED Display (3G3IV-PJVOP161)
Drive Mode Indicators
FWD:
REV:
SEQ:
Lit when there is a forward run command input.
Lit when there is a reverse run command input.
Lit when the run command from the control circuit
terminal is enabled.
REF:
Lit when the frequency reference from control circuit
terminals A1 and A2 is enabled.
ALARM: Lit when an error or alarm has occurred.
Data Display
Displays monitor data, parameter numbers, and
settings (in five digits).
Mode Display
DRIVE: Lit in Drive Mode.
QUICK: Lit in Quick Programming Mode.
ADV:
Lit in Advanced Programming Mode.
VERIFY: Lit in Verify Mode.
A. TUNE: Lit in Autotuning Mode.
Keys
Execute operations such as setting parameters,
monitoring, jogging, and autotuning.
Digital Operator with LCD Display (3G3IV-PJVOP160)
Drive Mode Indicators
FWD:
REV:
SEQ:
Lit when there is a forward run command input.
Lit when there is a reverse run command input.
Lit when the run command from the control circuit ter-
minal is enabled.
REF:
Lit when the frequency reference from control circuit
terminals A1 and A2 is enabled.
ALARM: Lit when an error or alarm has occurred.
Data Display
Displays monitor data, parameter numbers, and
settings.
Keys
Execute operations such as setting parameters,
monitoring, jogging, and autotuning.
4
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
3G3PV
3G3PV
Dimensions
T
Open Chassis Inverters (IP00)
Exterior diagrams of the Open Chassis Inverters are shown below.
A. 200-V class Inverters of 22 to 30 kW
400-V class Inverters of 22 to 55 kW
B. 200-V class Inverters of 37 to 110 kW
400-V class Inverters of 75 to 160 kW
T
Enclosed Wall-mounted Inverters (NEMA 1)
Exterior diagrams of the Enclosed Wall-mounted Inverters (NEMA 1) are shown below.
C. 200-V/400-V class Inverters of 0.4 to 18.5 kW
D. 200-V class Inverters of 22 to 75 kW
400-V class Inverters of 22 to 160 kW
(A 200-V class, 22-kW Inverter is shown as an example
sold only in Europe.)
5